Loading…

Comparison between the energy performance of a ground coupled water to water heat pump system and an air to water heat pump system for heating and cooling in typical conditions of the European Mediterranean coast

The investigation presented in this article was aimed at demonstrating the technical and economical feasibility of using ground source heat pump systems in mixed climate applications, where cooling requirements are dominant. We show an experimental comparison between a ground coupled heat pump syste...

Full description

Saved in:
Bibliographic Details
Published in:Energy conversion and management 2008-10, Vol.49 (10), p.2917-2923
Main Authors: Urchueguía, J.F., Zacarés, M., Corberán, J.M., Montero, Á., Martos, J., Witte, H.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:The investigation presented in this article was aimed at demonstrating the technical and economical feasibility of using ground source heat pump systems in mixed climate applications, where cooling requirements are dominant. We show an experimental comparison between a ground coupled heat pump system and a conventional air to water heat pump system, focussing at the heating and cooling energy performance. A direct comparison could be made as both systems are linked, in parallel, to the same building with exactly the same loads and climatic conditions. For a whole climatic season the results obtained show that the geothermal system saves, in terms of primary energy consumption, a 43 ± 17 % of the energy consumed by the conventional one when the system is working in heating mode, and a 37 ± 18 % when the system is working in cooling mode.
ISSN:0196-8904
1879-2227
DOI:10.1016/j.enconman.2008.03.001