Ac loss properties of a 1MVA single-phase HTS power transformer

We designed and built a single-phase 1 MVA-22/6.9 kV HTS transformer with the multi-layered cylindrical windings composed of Bi2223 parallel conductors. In advance of the design, the ac loss induced in the windings was estimated on the basis of the observed results in a strand. A subcooled liquid ni...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on applied superconductivity 2001-03, Vol.11 (1), p.1482-1485
Main Authors: IWAKUMA, Masataka, FUNAKI, Kazuo, MARUYAMA, Hiroshi, OGATA, Takenori, YOSHIDA, Shigeru, OHASHI, Kouichi, TSUTSUMI, Katsuya, HONDA, Kazuo, KAJIKAWA, Kazuhiro, TANAKA, Hideki, BOHNO, Takaaki, TOMIOKA, Akira, YAMADA, Hisao, NOSE, Shinichi, KONNO, Masayuki, YAGI, Yujiro
Format: Article
Language:English
Subjects:
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:We designed and built a single-phase 1 MVA-22/6.9 kV HTS transformer with the multi-layered cylindrical windings composed of Bi2223 parallel conductors. In advance of the design, the ac loss induced in the windings was estimated on the basis of the observed results in a strand. A subcooled liquid nitrogen cryogenic system with the corresponding cooling capacity was developed and attached to the transformer. The actual ac loss was measured by an electrical method. It was a great part of the total heat load and dominated the temperature rise of subcooled liquid nitrogen. We discussed the validity of the present estimation procedure of the ac loss in the windings as compared with the observed results.