Loading…
Application of extension theory to PD pattern recognition in high-voltage current transformers
This paper presents a novel partial-discharge (PD) recognition method based on the extension theory for high-voltage cast-resin current transformers (CRCTs). First, a commercial PD detector is used to measure the three-dimensional (3-D) PD patterns of the high-voltage CRCTs, then three data preproce...
Saved in:
Published in: | IEEE transactions on power delivery 2005-07, Vol.20 (3), p.1939-1946 |
---|---|
Main Authors: | , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | This paper presents a novel partial-discharge (PD) recognition method based on the extension theory for high-voltage cast-resin current transformers (CRCTs). First, a commercial PD detector is used to measure the three-dimensional (3-D) PD patterns of the high-voltage CRCTs, then three data preprocessing schemes that extract relevant features from the raw 3-D-PD patterns are presented for the proposed PD recognition method. Second, the matter-element models of the PD defect types are built according to PD patterns derived from practical experimental results. Then, the PD defect in a CRCT can be directly identified by degrees of correlation between the tested pattern and the matter-element models which have been built up. To demonstrate the effectiveness of the proposed method, comparative studies using a multilayer neural network and k-means algorithm are conducted on 150 sets of field-test PD patterns of 23-kV CRCTs with rather encouraging results. |
---|---|
ISSN: | 0885-8977 1937-4208 |
DOI: | 10.1109/TPWRD.2005.848673 |