Steady state frequency response of STATCOM
The paper develops analytical expressions for the admittances and impedances of a static synchronous compensator (STATCOM) as a function of frequency. The expressions include the conventional positive and negative sequence admittance as well as transfer admittances where a positive sequence current...
Saved in:
Published in: | IEEE transactions on power delivery 2001-01, Vol.16 (1), p.18-23 |
---|---|
Main Authors: | , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | The paper develops analytical expressions for the admittances and impedances of a static synchronous compensator (STATCOM) as a function of frequency. The expressions include the conventional positive and negative sequence admittance as well as transfer admittances where a positive sequence current generates a negative sequence voltage at another frequency. These results are then corroborated using the tool of electromagnetic transients simulation. The expressions are shown to be valid for six-pulse as well as higher pulse number configurations. The impact of the STATCOM's control system on the admittance is also investigated. |
---|---|
ISSN: | 0885-8977 1937-4208 |
DOI: | 10.1109/61.905574 |