Extract fan flow rates resulting in spillage
Experiments were carried out on open-flued gas and oil boilers in a test house at the Building Research Establishment, Garston, to find out what parameters affect combustion gas spillage. The experimentation consisted of testing the pressure difference and extract fan flow rate at which spillage occ...
Saved in:
Published in: | Building services engineering research & technology 1993-11, Vol.14 (4), p.143-149 |
---|---|
Main Author: | |
Format: | Article |
Language: | English |
Citations: | Items that this one cites |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Experiments were carried out on open-flued gas and oil boilers in a test house at the Building Research Establishment, Garston, to find out what parameters affect combustion gas spillage. The experimentation consisted of testing the pressure difference and extract fan flow rate at which spillage occurred. The results showed that in a large number of cases spillage will result if an open-flued gas appliance and air extract fan are running concurrently. Spillage was not encountered with the oil boiler which had a pressure jet burner. Any fan installed in the same room as an open flued gas appliance or an oil fired appliance with a vaporising plate burner should have a maximum capacity of 201 s-1, and fan and appliance should pass a suitable spillage test |
---|---|
ISSN: | 0143-6244 1477-0849 |
DOI: | 10.1177/014362449301400404 |