Loading…

Modeling cooling tower fouling in helical-rib tubes based on Von-Karman analogy

This paper provides an analysis on cooling tower fouling data taken in seven 15.54 mm I.D. helically ribbed, copper tubes at R e = 16,000. The geometric parameters include number of rib starts, helix angle, and height. A series of semi-theoretical fouling correlations as a function of the product of...

Full description

Saved in:
Bibliographic Details
Published in:International journal of heat and mass transfer 2010-06, Vol.53 (13), p.2715-2721
Main Authors: Li, Wei, Li, Guanqiu
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:This paper provides an analysis on cooling tower fouling data taken in seven 15.54 mm I.D. helically ribbed, copper tubes at R e = 16,000. The geometric parameters include number of rib starts, helix angle, and height. A series of semi-theoretical fouling correlations as a function of the product of area indexes and efficiency indexes are developed. The mass transfer coefficient is calculated by the Von-Karman analogy. The wall shear stress is obtained from the pressure drop. The correlations and the analyses can be used directly to assess the fouling potential of helical-rib in actual cooling water systems.
ISSN:0017-9310
1879-2189
DOI:10.1016/j.ijheatmasstransfer.2010.02.034