Workers' exposure to electric fields during the task 'maintenance of an operating device of circuit breaker from a service platform' at 110-kV substations
The objective of the study was to investigate occupational exposure to electric fields during the task 'maintenance of an operating device of circuit breaker from a service platform' at 110-kV substations. The aim was also to compare the results to Directive 2013/35/EU. At 16 substations,...
Saved in:
Published in: | International journal of occupational safety and ergonomics 2019-01, Vol.25 (1), p.161-164 |
---|---|
Main Authors: | , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | The objective of the study was to investigate occupational exposure to electric fields during the task 'maintenance of an operating device of circuit breaker from a service platform' at 110-kV substations. The aim was also to compare the results to Directive 2013/35/EU. At 16 substations, 255 electric field measurements were performed. The highest mean value of the electric fields was 9.6 kV⋅m
−1
. At 63% of substations the maximum values were over 10.0 kV⋅m
−1
, and at 31% of the substations the 75th percentiles were over 10.0 kV⋅m
−1
, which is the low action level (AL) according to Directive 2013/35/EU. All measured values were below the high AL (20.0 kV⋅m
−1
). In the future, it is important to take into account that the measurements were only taken at Finnish 110-kV substations; therefore, it is not possible to generalize these results to other countries and different types of substations. |
---|---|
ISSN: | 1080-3548 2376-9130 |
DOI: | 10.1080/10803548.2018.1433579 |