Simplified protection algorithm for fault detection and localization in DC microgrid

In a microgrid, conventional overcurrent and current direction based protection techniques have limitations during high resistance faults. Besides, ring configuration microgrids offer bidirectional power flow rather than unidirectional power flow. Moreover, DC microgrids own low line resistance and...

Full description

Saved in:
Bibliographic Details
Published in:Electric power systems research 2022-10, Vol.211, p.108229, Article 108229
Main Authors: Nageswara Reddy, Nareddy, Velpula, Rajesh, Raja, P., Moorthi, S.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
cited_by cdi_FETCH-LOGICAL-c230t-8a1d81bb418fa7a3a22e552a1d93559afda338b429b8aa93550b408417979acb3
cites cdi_FETCH-LOGICAL-c230t-8a1d81bb418fa7a3a22e552a1d93559afda338b429b8aa93550b408417979acb3
container_end_page
container_issue
container_start_page 108229
container_title Electric power systems research
container_volume 211
creator Nageswara Reddy, Nareddy
Velpula, Rajesh
Raja, P.
Moorthi, S.
description In a microgrid, conventional overcurrent and current direction based protection techniques have limitations during high resistance faults. Besides, ring configuration microgrids offer bidirectional power flow rather than unidirectional power flow. Moreover, DC microgrids own low line resistance and high DC link capacitance; it results in an immense increase in current. During fault conditions, it may cause an undesirable disconnection of resources and make the system unreliable. An accurate and fast operating protection strategy is needed to explore and achieve the above mentioned challenges. To start, with the difference in consecutive current sample data, the current difference index has been evaluated. The non-zero index is granting the estimation of frequency using natural characteristics of fault current, which correctly discriminates an incipient fault and sudden switching loads. Thereafter, by adopting local voltage and current samples during the fault, estimated inductance has been exploited, which possesses polarity and magnitude to isolate the fault and identify the fault position, respectively. The proposed method genuineness for numerous cases like low and high resistance faults at various locations, including close-in faults, bidirectional power flow, different load conditions, and other configurations is validated in MATLAB/Simulink environment. This method precisely estimates fault location under the aforementioned cases. A comparative study of the proposed scheme with existing protection methods has been carried out, proving that this method is more accurate and enhances the relay dependability. •The non-zero value of current difference index triggers the fault detection algorithm.•The estimation of frequency is adopted to discriminate fault inception, load change.•The estimation of inductance is used to isolate fault line and to find fault location.•The proposed protection algorithm works effectively even during high resistance fault.•Comparative study of proposed method with the methods in literature has been done.
doi_str_mv 10.1016/j.epsr.2022.108229
format article
fullrecord <record><control><sourceid>elsevier_cross</sourceid><recordid>TN_cdi_crossref_primary_10_1016_j_epsr_2022_108229</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><els_id>S0378779622004370</els_id><sourcerecordid>S0378779622004370</sourcerecordid><originalsourceid>FETCH-LOGICAL-c230t-8a1d81bb418fa7a3a22e552a1d93559afda338b429b8aa93550b408417979acb3</originalsourceid><addsrcrecordid>eNp9kMlOwzAQhn0AibK8ACe_QIqXpLYlLqisUiUOlLM1ie0yVRJHdkCCpyehiCOnkb7RP8tHyCVnS8746mq_9ENOS8GEmIAWwhyRBZNKF0qZ1Qk5zXnPGFsZVS3I9gW7ocWA3tEhxdE3I8aeQruLCce3joaYaID3dqTO_3V7R9vYQItf8AOwp7dr2mGT4i6hOyfHAdrsL37rGXm9v9uuH4vN88PT-mZTNEKysdDAneZ1XXIdQIEEIXxViYkaWVUGggMpdV0KU2uAmbG6ZLrkyigDTS3PiDjMnfbmnHywQ8IO0qflzM4u7N7OLuzswh5cTKHrQ8hPl32gTzY36PvGO0zTf9ZF_C_-DeiSazM</addsrcrecordid><sourcetype>Aggregation Database</sourcetype><iscdi>true</iscdi><recordtype>article</recordtype></control><display><type>article</type><title>Simplified protection algorithm for fault detection and localization in DC microgrid</title><source>Elsevier</source><creator>Nageswara Reddy, Nareddy ; Velpula, Rajesh ; Raja, P. ; Moorthi, S.</creator><creatorcontrib>Nageswara Reddy, Nareddy ; Velpula, Rajesh ; Raja, P. ; Moorthi, S.</creatorcontrib><description>In a microgrid, conventional overcurrent and current direction based protection techniques have limitations during high resistance faults. Besides, ring configuration microgrids offer bidirectional power flow rather than unidirectional power flow. Moreover, DC microgrids own low line resistance and high DC link capacitance; it results in an immense increase in current. During fault conditions, it may cause an undesirable disconnection of resources and make the system unreliable. An accurate and fast operating protection strategy is needed to explore and achieve the above mentioned challenges. To start, with the difference in consecutive current sample data, the current difference index has been evaluated. The non-zero index is granting the estimation of frequency using natural characteristics of fault current, which correctly discriminates an incipient fault and sudden switching loads. Thereafter, by adopting local voltage and current samples during the fault, estimated inductance has been exploited, which possesses polarity and magnitude to isolate the fault and identify the fault position, respectively. The proposed method genuineness for numerous cases like low and high resistance faults at various locations, including close-in faults, bidirectional power flow, different load conditions, and other configurations is validated in MATLAB/Simulink environment. This method precisely estimates fault location under the aforementioned cases. A comparative study of the proposed scheme with existing protection methods has been carried out, proving that this method is more accurate and enhances the relay dependability. •The non-zero value of current difference index triggers the fault detection algorithm.•The estimation of frequency is adopted to discriminate fault inception, load change.•The estimation of inductance is used to isolate fault line and to find fault location.•The proposed protection algorithm works effectively even during high resistance fault.•Comparative study of proposed method with the methods in literature has been done.</description><identifier>ISSN: 0378-7796</identifier><identifier>DOI: 10.1016/j.epsr.2022.108229</identifier><language>eng</language><publisher>Elsevier B.V</publisher><subject>DC microgrid protection ; Directional comparison scheme ; Estimated inductance ; Fault detection ; Frequency of oscillation</subject><ispartof>Electric power systems research, 2022-10, Vol.211, p.108229, Article 108229</ispartof><rights>2022</rights><lds50>peer_reviewed</lds50><woscitedreferencessubscribed>false</woscitedreferencessubscribed><citedby>FETCH-LOGICAL-c230t-8a1d81bb418fa7a3a22e552a1d93559afda338b429b8aa93550b408417979acb3</citedby><cites>FETCH-LOGICAL-c230t-8a1d81bb418fa7a3a22e552a1d93559afda338b429b8aa93550b408417979acb3</cites><orcidid>0000-0002-6426-5740 ; 0000-0002-2721-3757 ; 0000-0003-4821-9418</orcidid></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><link.rule.ids>314,780,784,27924,27925</link.rule.ids></links><search><creatorcontrib>Nageswara Reddy, Nareddy</creatorcontrib><creatorcontrib>Velpula, Rajesh</creatorcontrib><creatorcontrib>Raja, P.</creatorcontrib><creatorcontrib>Moorthi, S.</creatorcontrib><title>Simplified protection algorithm for fault detection and localization in DC microgrid</title><title>Electric power systems research</title><description>In a microgrid, conventional overcurrent and current direction based protection techniques have limitations during high resistance faults. Besides, ring configuration microgrids offer bidirectional power flow rather than unidirectional power flow. Moreover, DC microgrids own low line resistance and high DC link capacitance; it results in an immense increase in current. During fault conditions, it may cause an undesirable disconnection of resources and make the system unreliable. An accurate and fast operating protection strategy is needed to explore and achieve the above mentioned challenges. To start, with the difference in consecutive current sample data, the current difference index has been evaluated. The non-zero index is granting the estimation of frequency using natural characteristics of fault current, which correctly discriminates an incipient fault and sudden switching loads. Thereafter, by adopting local voltage and current samples during the fault, estimated inductance has been exploited, which possesses polarity and magnitude to isolate the fault and identify the fault position, respectively. The proposed method genuineness for numerous cases like low and high resistance faults at various locations, including close-in faults, bidirectional power flow, different load conditions, and other configurations is validated in MATLAB/Simulink environment. This method precisely estimates fault location under the aforementioned cases. A comparative study of the proposed scheme with existing protection methods has been carried out, proving that this method is more accurate and enhances the relay dependability. •The non-zero value of current difference index triggers the fault detection algorithm.•The estimation of frequency is adopted to discriminate fault inception, load change.•The estimation of inductance is used to isolate fault line and to find fault location.•The proposed protection algorithm works effectively even during high resistance fault.•Comparative study of proposed method with the methods in literature has been done.</description><subject>DC microgrid protection</subject><subject>Directional comparison scheme</subject><subject>Estimated inductance</subject><subject>Fault detection</subject><subject>Frequency of oscillation</subject><issn>0378-7796</issn><fulltext>true</fulltext><rsrctype>article</rsrctype><creationdate>2022</creationdate><recordtype>article</recordtype><recordid>eNp9kMlOwzAQhn0AibK8ACe_QIqXpLYlLqisUiUOlLM1ie0yVRJHdkCCpyehiCOnkb7RP8tHyCVnS8746mq_9ENOS8GEmIAWwhyRBZNKF0qZ1Qk5zXnPGFsZVS3I9gW7ocWA3tEhxdE3I8aeQruLCce3joaYaID3dqTO_3V7R9vYQItf8AOwp7dr2mGT4i6hOyfHAdrsL37rGXm9v9uuH4vN88PT-mZTNEKysdDAneZ1XXIdQIEEIXxViYkaWVUGggMpdV0KU2uAmbG6ZLrkyigDTS3PiDjMnfbmnHywQ8IO0qflzM4u7N7OLuzswh5cTKHrQ8hPl32gTzY36PvGO0zTf9ZF_C_-DeiSazM</recordid><startdate>202210</startdate><enddate>202210</enddate><creator>Nageswara Reddy, Nareddy</creator><creator>Velpula, Rajesh</creator><creator>Raja, P.</creator><creator>Moorthi, S.</creator><general>Elsevier B.V</general><scope>AAYXX</scope><scope>CITATION</scope><orcidid>https://orcid.org/0000-0002-6426-5740</orcidid><orcidid>https://orcid.org/0000-0002-2721-3757</orcidid><orcidid>https://orcid.org/0000-0003-4821-9418</orcidid></search><sort><creationdate>202210</creationdate><title>Simplified protection algorithm for fault detection and localization in DC microgrid</title><author>Nageswara Reddy, Nareddy ; Velpula, Rajesh ; Raja, P. ; Moorthi, S.</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-c230t-8a1d81bb418fa7a3a22e552a1d93559afda338b429b8aa93550b408417979acb3</frbrgroupid><rsrctype>articles</rsrctype><prefilter>articles</prefilter><language>eng</language><creationdate>2022</creationdate><topic>DC microgrid protection</topic><topic>Directional comparison scheme</topic><topic>Estimated inductance</topic><topic>Fault detection</topic><topic>Frequency of oscillation</topic><toplevel>peer_reviewed</toplevel><toplevel>online_resources</toplevel><creatorcontrib>Nageswara Reddy, Nareddy</creatorcontrib><creatorcontrib>Velpula, Rajesh</creatorcontrib><creatorcontrib>Raja, P.</creatorcontrib><creatorcontrib>Moorthi, S.</creatorcontrib><collection>CrossRef</collection><jtitle>Electric power systems research</jtitle></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext</fulltext></delivery><addata><au>Nageswara Reddy, Nareddy</au><au>Velpula, Rajesh</au><au>Raja, P.</au><au>Moorthi, S.</au><format>journal</format><genre>article</genre><ristype>JOUR</ristype><atitle>Simplified protection algorithm for fault detection and localization in DC microgrid</atitle><jtitle>Electric power systems research</jtitle><date>2022-10</date><risdate>2022</risdate><volume>211</volume><spage>108229</spage><pages>108229-</pages><artnum>108229</artnum><issn>0378-7796</issn><abstract>In a microgrid, conventional overcurrent and current direction based protection techniques have limitations during high resistance faults. Besides, ring configuration microgrids offer bidirectional power flow rather than unidirectional power flow. Moreover, DC microgrids own low line resistance and high DC link capacitance; it results in an immense increase in current. During fault conditions, it may cause an undesirable disconnection of resources and make the system unreliable. An accurate and fast operating protection strategy is needed to explore and achieve the above mentioned challenges. To start, with the difference in consecutive current sample data, the current difference index has been evaluated. The non-zero index is granting the estimation of frequency using natural characteristics of fault current, which correctly discriminates an incipient fault and sudden switching loads. Thereafter, by adopting local voltage and current samples during the fault, estimated inductance has been exploited, which possesses polarity and magnitude to isolate the fault and identify the fault position, respectively. The proposed method genuineness for numerous cases like low and high resistance faults at various locations, including close-in faults, bidirectional power flow, different load conditions, and other configurations is validated in MATLAB/Simulink environment. This method precisely estimates fault location under the aforementioned cases. A comparative study of the proposed scheme with existing protection methods has been carried out, proving that this method is more accurate and enhances the relay dependability. •The non-zero value of current difference index triggers the fault detection algorithm.•The estimation of frequency is adopted to discriminate fault inception, load change.•The estimation of inductance is used to isolate fault line and to find fault location.•The proposed protection algorithm works effectively even during high resistance fault.•Comparative study of proposed method with the methods in literature has been done.</abstract><pub>Elsevier B.V</pub><doi>10.1016/j.epsr.2022.108229</doi><orcidid>https://orcid.org/0000-0002-6426-5740</orcidid><orcidid>https://orcid.org/0000-0002-2721-3757</orcidid><orcidid>https://orcid.org/0000-0003-4821-9418</orcidid></addata></record>
fulltext fulltext
identifier ISSN: 0378-7796
ispartof Electric power systems research, 2022-10, Vol.211, p.108229, Article 108229
issn 0378-7796
language eng
recordid cdi_crossref_primary_10_1016_j_epsr_2022_108229
source Elsevier
subjects DC microgrid protection
Directional comparison scheme
Estimated inductance
Fault detection
Frequency of oscillation
title Simplified protection algorithm for fault detection and localization in DC microgrid
url http://sfxeu10.hosted.exlibrisgroup.com/loughborough?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2024-12-29T00%3A46%3A01IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-elsevier_cross&rft_val_fmt=info:ofi/fmt:kev:mtx:journal&rft.genre=article&rft.atitle=Simplified%20protection%20algorithm%20for%20fault%20detection%20and%20localization%20in%20DC%20microgrid&rft.jtitle=Electric%20power%20systems%20research&rft.au=Nageswara%20Reddy,%20Nareddy&rft.date=2022-10&rft.volume=211&rft.spage=108229&rft.pages=108229-&rft.artnum=108229&rft.issn=0378-7796&rft_id=info:doi/10.1016/j.epsr.2022.108229&rft_dat=%3Celsevier_cross%3ES0378779622004370%3C/elsevier_cross%3E%3Cgrp_id%3Ecdi_FETCH-LOGICAL-c230t-8a1d81bb418fa7a3a22e552a1d93559afda338b429b8aa93550b408417979acb3%3C/grp_id%3E%3Coa%3E%3C/oa%3E%3Curl%3E%3C/url%3E&rft_id=info:oai/&rft_id=info:pmid/&rfr_iscdi=true