Design and Test Results of a 1 MVA Resistive Type Fault Current Limiter

The 1 MVA resistive type single phase AC fault current limiter (FCL) was build and successfully tested by capacitors battery discharge. FCL rated voltage is 3.5kV, current 250 Arms. The 240 m of HTS tape (type SF12100 by SupePower) was used for FCL production. The FCL consists of 8 bifilar coils eac...

Full description

Saved in:
Bibliographic Details
Published in:Physics procedia 2012, Vol.36, p.1215-1218
Main Authors: Keilin, V.E., Lobyntsev, V.V., Novikov, M.S., Novikov, S.J., Shcherbakov, V.I.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:The 1 MVA resistive type single phase AC fault current limiter (FCL) was build and successfully tested by capacitors battery discharge. FCL rated voltage is 3.5kV, current 250 Arms. The 240 m of HTS tape (type SF12100 by SupePower) was used for FCL production. The FCL consists of 8 bifilar coils each wound onto glass-fiber 70mm diameter tube and connected in series. The HTS tapes were additionally stabilized with Cu laminated highly resistive foil. During the tests of separate FCL coils at 380V an excellent limiting performance was observed. Tested FCL coil was switched off after 75ms, the maximum temperature at the HTS tape was less then 230K, the recovery time was about 5 s.