Loading…
Robust Model Predictive Control (MPC) for large-scale PV plant based on paralleled three-phase inverters
•This paper focuses on the grid integration of a large-scale photovoltaic plant through paralleled inverters.•Robust model predictive control is proposed to enhance the power quality.•Optimization approach is used to minimize circulating currents in parallel inverters.•Simulation comparisons with co...
Saved in:
Published in: | Solar energy 2020-05, Vol.202, p.409-419 |
---|---|
Main Authors: | , , , , , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | •This paper focuses on the grid integration of a large-scale photovoltaic plant through paralleled inverters.•Robust model predictive control is proposed to enhance the power quality.•Optimization approach is used to minimize circulating currents in parallel inverters.•Simulation comparisons with conventional control confirm the superiority of the proposed approach.
In this contribution a robust Model Predictive Control (MPC) is proposed to enhance the power quality of a large-scale PV plant connected to the grid through Paralleled Voltage Source Inverters (PVSIs) with common AC and DC buses. Paralleling inverters allow handling high-power export and offer advantages in terms of redundancy which ensure the system reliability. However, due to the physical differences and parameter disparities between the inverters, zero sequence circulating currents will flow through it, which will disturb the performance of the system. Hence, the control goal is to regulate the currents injected into the grid, suppress the zero-sequence circulating current (ZSCC). Consequently, this study proposes an MPC algorithm that is based on optimization approach which allows minimizing circulating currents. In order to show its effectiveness and performance of the proposed control, a comparison with linear PI controller is included. In addition, design control and tuning procedure are detailed. Simulation results show the performance of the proposed controller in ensuring power quality, and suppressing circulating currents. To verify the real-time feasibility of the proposed control scheme, Hardware-In-the-Loop (HIL) setup is carried out with means of Opal-RT and dSPACE rapid prototyping systems. |
---|---|
ISSN: | 0038-092X 1471-1257 |
DOI: | 10.1016/j.solener.2020.03.091 |