Effects of Grounding Impedance on the Second Harmonic Component Produced by GIC Flows
Geomagnetic disturbances trigger quasi-dc currents that flow through grounding circuits into power systems, mostly through power transformers. Geomagnetically-induced currents (GICs) can cause severe harmonic distortions, disruption in reactive power flow, and/or thermal damage to power transformers...
Saved in:
Main Authors: | , , , , , , |
---|---|
Format: | Conference Proceeding |
Language: | English |
Subjects: | |
Online Access: | Request full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Geomagnetic disturbances trigger quasi-dc currents that flow through grounding circuits into power systems, mostly through power transformers. Geomagnetically-induced currents (GICs) can cause severe harmonic distortions, disruption in reactive power flow, and/or thermal damage to power transformers. These adverse effects of GIC flows on power transformers depend on the GIC magnitude, transformer core design, grounding circuit, and winding configuration. This paper analyzes the effects of grounding circuit designs on the adverse impacts of GIC flows in power transformers. These effects are analyzed through experimental tests carried out using laboratory 3ϕ, multi-core power transformers. Experimental tests are performed for several grounding circuit designs for the test power transformers. Normal, magnetizing inrush, line-to-line, and line-to-neutral fault conditions are conducted for each tested grounding circuit design. Results of experimental tests show that grounding circuits with low impedance have minor effects on the GIC flows, while grounding circuits with high impedance tend to reduce the magnitude of the GIC. In addition, test results demonstrate that grounding circuits have little influence on the harmonic distortion (mainly the 2 nd harmonic component) created by a GIC flow. |
---|---|
ISSN: | 2158-4907 |
DOI: | 10.1109/ICPS60943.2024.10563240 |