Loading…
A first principles framework to predict the transient performance of latent heat thermal energy storage
Thermal energy storage (TES) is increasingly recognized as an essential component of efficient Combined Heat and Power (CHP), Concentrated Solar Power (CSP), Heating Ventilation and Air Conditioning (HVAC), and refrigeration as it reduces peak demand while helping to manage intermittent availability...
Saved in:
Published in: | Journal of energy storage 2021-04, Vol.36 (C), p.102388, Article 102388 |
---|---|
Main Authors: | , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Thermal energy storage (TES) is increasingly recognized as an essential component of efficient Combined Heat and Power (CHP), Concentrated Solar Power (CSP), Heating Ventilation and Air Conditioning (HVAC), and refrigeration as it reduces peak demand while helping to manage intermittent availability of energy (e.g., from solar or wind). Latent Heat Thermal Energy Storage (LHTES) is a viable option because of its high energy storage density. Parametric analysis of LHTES in terms of dimensionless numbers is highly desired as a tool to model LHTES systems. One approach is to develop a model equation so as to minimize the error between the model and data obtained from experiments or simulations. While this approach can produce an accurate correlation applicable within the range of data used for its creation, it does not provide physical understanding of the rate-limiting process controlling the transient behavior of the device. In this paper we present an alternative approach whereby the potential rate-limiting processes are identified from first principles and then the key process is determined as a function of time as a LHTES device is charged. For example, in a simple geometry, the melt-fraction can be expected to vary linearly in time if the heat transfer rate is limited by natural convection of the phase changing material and we show it scales with the PCM Grashof number asGrp1 and PCM Prandtl number asPrp(1∕3). On the other hand, if surface area of solid PCM limits the heat transfer rate, the melt fraction increases asymptotically to reach full melting. The existence of these linear and asymptotic regions and theGrp1Prp1∕3 shape of the melt fraction curve is verified using our database of 64 simulations. Of practical importance in designing LHTES devices is the melt fraction at which the heat transfer rate ceases to be limited by convection, after which the heat storage rate deteriorates. For our geometry, this is found to be about 90%. This test case of our methodology shows the value of our approach, that predicting heat storage rate based on the rate-limiting physical phenomenon as a function of time is an effective approach to modeling LHTES devices.
•A framework is developed from first principles to systematically analyze LHTES.•The transient melt fraction is correlated to the PCM Grashof and Prandtl numbers.•The correlation is confirmed using 64 Finite Volume Method simulations.•A critical melt fraction that marks transition between regimes is dete |
---|---|
ISSN: | 2352-152X 2352-1538 |
DOI: | 10.1016/j.est.2021.102388 |