Prediction and Characterization of Dry-out Heat Flux in Micropillar Wick Structures

Thin-film evaporation in wick structures for cooling high-performance electronic devices is attractive because it harnesses the latent heat of vaporization and does not require external pumping. However, optimizing the wick structures to increase the dry-out heat flux is challenging due to the compl...

Full description

Saved in:
Bibliographic Details
Published in:Langmuir 2016-02, Vol.32 (7), p.1920-1927
Main Authors: Zhu, Yangying, Antao, Dion S, Lu, Zhengmao, Somasundaram, Sivanand, Zhang, Tiejun, Wang, Evelyn N
Format: Article
Language:English
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Thin-film evaporation in wick structures for cooling high-performance electronic devices is attractive because it harnesses the latent heat of vaporization and does not require external pumping. However, optimizing the wick structures to increase the dry-out heat flux is challenging due to the complexities in modeling the liquid–vapor interface and the flow through the wick structures. In this work, we developed a model for thin-film evaporation from micropillar array wick structures and validated the model with experiments. The model numerically simulates liquid velocity, pressure, and meniscus curvature along the wicking direction by conservation of mass, momentum, and energy based on a finite volume approach. Specifically, the three-dimensional meniscus shape, which varies along the wicking direction with the local liquid pressure, is accurately captured by a force balance using the Young–Laplace equation. The dry-out condition is determined when the minimum contact angle on the pillar surface reaches the receding contact angle as the applied heat flux increases. With this model, we predict the dry-out heat flux on various micropillar structure geometries (diameter, pitch, and height) in the length scale range of 1–100 μm and discuss the optimal geometries to maximize the dry-out heat flux. We also performed detailed experiments to validate the model predictions, which show good agreement. This work provides insights into the role of surface structures in thin-film evaporation and offers important design guidelines for enhanced thermal management of high-performance electronic devices.
ISSN:0743-7463
1520-5827
DOI:10.1021/acs.langmuir.5b04502