Loading…

Analysis of the Influence of Transient Process During the Shunt Reactors Commutation on Insulation of Substation "Zarya" Auxiliaries

This article considers the modeling and analysis of transient processes in a system of substation Zarya500 kV with different external conditions during commutation shunt reactor ROMBS-60000/500. Revealed that the high-frequency over voltage during switching shunt reactor of 500 kV, can be dangerous...

Full description

Saved in:
Bibliographic Details
Published in:Journal of Siberian Federal University. Engineering & Technologies 2016-02, Vol.9 (2), p.225-225
Main Authors: Sizganova, Evgenia U, Petukhov, Roman A, Sizganov, Nikita V, Nikotina, Daria U
Format: Article
Language:eng ; rus
Subjects:
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:This article considers the modeling and analysis of transient processes in a system of substation Zarya500 kV with different external conditions during commutation shunt reactor ROMBS-60000/500. Revealed that the high-frequency over voltage during switching shunt reactor of 500 kV, can be dangerous for air insulation transformers TSZ-630/15.